MLM冷凍渦旋壓縮機 | 
|
壓縮機命名
|
性能參數 |
技術參數
|
運行界限 |
運行工況
|
尺寸與接管 |
MLM冷凍渦旋壓縮機
型號 |
參數 |
冷凝溫度 |
蒸發溫度(0℃) |
(0℃) |
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
MLM019T4 |
制冷量(W) |
16 |
3,843 |
4,599 |
5,489 |
6,530 |
|
|
|
20 |
3,737 |
4,493 |
5,383 |
6,420 |
7,620 |
|
|
30 |
3,393 |
4,129 |
4,992 |
5,997 |
7,160 |
8,493 |
10,012 |
40 |
|
|
4,492 |
5,432 |
6,524 |
7,781 |
9,218 |
50 |
|
|
|
4,811 |
5,799 |
6,946 |
8,269 |
60 |
|
|
|
|
|
6,077 |
7,251 |
68 |
|
|
|
|
|
|
6,447 |
|
|
|
|
|
|
|
|
|
輸入功率(W) |
16 |
1,250 |
1,076 |
993 |
980 |
|
|
|
20 |
1,358 |
1,188 |
1,104 |
1,088 |
1,118 |
|
|
30 |
1,621 |
1,466 |
1,389 |
1,371 |
1,392 |
1,431 |
1,468 |
40 |
|
|
1,704 |
1,694 |
1,714 |
1,745 |
1,765 |
50 |
|
|
|
2,080 |
2,110 |
2,141 |
2,154 |
60 |
|
|
|
|
|
2,645 |
2,660 |
68 |
|
|
|
|
|
|
3,165 |
MLM021T4 |
制冷量(W) |
16 |
4,150 |
5,004 |
5,974 |
7,084 |
|
|
|
20 |
3,954 |
4,814 |
5,786 |
6,895 |
8,165 |
|
|
30 |
3,482 |
4,330 |
5,282 |
6,362 |
7,596 |
9,009 |
10,625 |
40 |
|
|
4,751 |
5,767 |
6,928 |
8,260 |
9,788 |
50 |
|
|
|
5,138 |
6,190 |
7,404 |
8,807 |
60 |
|
|
|
|
|
6,471 |
7,711 |
68 |
|
|
|
|
|
|
6,772 |
|
|
|
|
|
|
|
|
|
輸入功率(W) |
16 |
1,178 |
1,071 |
1,046 |
1,075 |
|
|
|
20 |
1,329 |
1,209 |
1,175 |
1,197 |
1,248 |
|
|
30 |
1,703 |
1,552 |
1,492 |
1,495 |
1,532 |
1,578 |
1,603 |
40 |
|
|
1,854 |
1,835 |
1,858 |
1,895 |
1,917 |
50 |
|
|
|
2,286 |
2,292 |
2,318 |
2,335 |
60 |
|
|
|
|
|
2,915 |
2,926 |
68 |
|
|
|
|
|
|
3,567 |
MLM026T4 |
制冷量(W) |
16 |
4,897 |
6,122 |
7,397 |
8,821 |
|
|
|
20 |
4,705 |
5,941 |
7,216 |
8,630 |
10,283 |
|
|
30 |
4,189 |
5,424 |
6,672 |
8,033 |
9,608 |
11,496 |
13,796 |
40 |
|
|
6,048 |
7,319 |
8,777 |
10,522 |
12,655 |
50 |
|
|
|
6,548 |
7,851 |
9,415 |
11,341 |
60 |
|
|
|
|
|
8,238 |
9,919 |
68 |
|
|
|
|
|
|
8,745 |
|
|
|
|
|
|
|
|
|
輸入功率(W) |
16 |
1,486 |
1,314 |
1,238 |
1,226 |
|
|
|
20 |
1,583 |
1,418 |
1,348 |
1,342 |
1,369 |
|
|
30 |
1,900 |
1,742 |
1,680 |
1,681 |
1,715 |
1,749 |
1,751 |
40 |
|
|
2,121 |
2,119 |
2,148 |
2,177 |
2,175 |
50 |
|
|
|
2,689 |
2,703 |
2,716 |
2,698 |
60 |
|
|
|
|
|
3,402 |
3,357 |
68 |
|
|
|
|
|
|
4,005 |
MLM030T4 |
制冷量(W) |
16 |
6 |
7,350 |
8,790 |
10,421 |
|
|
|
20 |
5,827 |
7,159 |
8,604 |
10,229 |
12,098 |
|
|
30 |
5,159 |
6,514 |
7,953 |
9,540 |
11,341 |
14,320 |
15,842 |
40 |
|
|
7,119 |
8,638 |
10,341 |
12,291 |
14,554 |
50 , P> |
|
|
|
7,627 |
9,201 |
10,992 |
13,066 |
60 |
|
|
|
|
|
9,629 |
11,483 |
68 |
|
|
|
|
|
|
10,218 |
|
|
|
|
|
|
|
|
|
輸入功率(W) |
16 |
2,730 |
2,068 |
1,706 |
1,569 |
|
|
|
20 |
2,872 |
2,218 |
1,861 |
1,726 |
1,736 |
|
|
30 |
3,247 |
2,614 |
2,271 |
2,142 |
2,151 |
2,222 |
2,279 |
40 |
|
|
2,755 |
2,634 |
2,643 |
2,706 |
2,747 |
50 |
|
|
|
3,254 |
3,264 |
3,221 |
3,349 |
60 |
|
|
|
|
|
4,119 |
4,134 |
68 |
|
|
|
|
|
|
4,931 |
MLM038T4 |
制冷量(W) |
16 |
6,283 |
8,198 |
10,188 |
12,319 |
|
|
|
20 |
6,076 |
7,957 |
9,916 |
12,017 |
14,326 |
|
|
30 |
5,531 |
7,289 |
9,131 |
11,122 |
13,326 |
15,810 |
18,639 |
40 |
|
|
8,257 |
10,083 |
12,129 |
14,461 |
17,143 |
50 |
|
|
|
8,972 |
10,806 |
12,933 |
15,416 |
60 |
|
|
|
|
|
11,296 |
13,526 |
68 |
|
|
|
|
|
|
11,947 |
輸入功率(W) |
16 |
2,472 |
2,065 |
1,880 |
1,855 |
|
|
|
20 |
2,685 |
2,266 |
2,072 |
2,038 |
2,101 |
|
|
30 |
3,249 |
2,799 |
2,579 |
2,524 |
2,571 |
2,655 |
2,715 |
40 |
|
|
3,187 |
3,110 |
3,139 |
3,211 |
3,262 |
50 |
|
|
|
3,870 |
3,881 |
3,939 |
3,981 |
60 |
|
|
|
|
|
4,914 |
4,946 |
68 |
|
|
|
|
|
|
5,944 |
MLM045T4 |
制冷量(W) |
16 |
9,493 |
10,826 |
12,735 |
15,195 |
|
|
|
20 |
9,281 |
10,565 |
12,416 |
14,806 |
17,710 |
|
|
30 |
8,672 |
9,827 |
11,521 |
13,728 |
16,424 |
19,581 |
23,174 |
40 |
|
|
10,498 |
12,511 |
14,985 |
17,895 |
21,215 |
50 |
|
|
|
11,162 |
13,403 |
16,054 |
19,088 |
60 |
|
|
|
|
|
14,067 |
16,803 |
68 |
|
|
|
|
|
|
14,867 |
輸入功率(W) |
16 |
1,533 |
1,874 |
2,073 |
2,184 |
|
|
|
20 |
1,731 |
2,081 |
2,283 |
2,389 |
2,455 |
|
|
30 |
2,280 |
2,663 |
2,879 |
2,982 |
3,028 |
3,068 |
3,159 |
40 |
|
|
3,607 |
3,720 |
3,757 |
3,772 |
3,818 |
50 |
|
|
|
4,639 |
4,681 |
4,682 |
4,698 |
60 |
|
|
|
|
|
5,838 |
5,835 |
68 |
|
|
|
|
|
|
6,956 |
MLM048T4 |
制冷量(W) |
16 |
8,315 |
11,033 |
13,844 |
16,844 |
|
|
|
20 |
7,904 |
10,588 |
13,307 |
16,247 |
19,474 |
|
|
30 |
7,141 |
9,591 |
12,139 |
14,884 |
17,922 |
21,348 |
25,259 |
40 |
|
|
11,095 |
13,582 |
16,367 |
19,547 |
23,216 |
50 |
|
|
|
12,180 |
14,650 |
17,520 |
20,885 |
60 |
|
|
|
|
|
15,106 |
18,105 |
68 |
|
|
|
|
|
|
15,449 |
輸入功率(W) |
16 |
1,438 |
1904 |
2,195 |
2,365 |
|
|
|
20 |
1,701 |
2160 |
2,443 |
2,602 |
2,692 |
|
|
30 |
2,412 |
2857 |
3,121 |
3,258 |
3,322 |
3,366 |
3,444 |
40 |
|
|
3,937 |
4,056 |
4,099 |
4,118 |
4,167 |
50 |
|
|
|
5,061 |
5,088 |
5,087 |
5,112 |
60 |
|
|
|
|
|
6,337 |
6,343 |
68 |
|
|
|
|
|
|
7,578 |
MLM058T4 |
制冷量(W) |
16 |
10,975 |
13361 |
16,297 |
19,790 |
|
|
|
20 |
10,454 |
12790 |
15,663 |
19,077 |
23,038 |
|
|
30 |
9,307 |
11521 |
14,234 |
17,451 |
21,180 |
25,424 |
30,190 |
40 |
|
|
12,818 |
15,840 |
19,336 |
23,311 |
27,771 |
50 |
|
|
|
13,978 |
17,242 |
20,950 |
25,105 |
60 |
|
|
|
|
|
18,075 |
21,927 |
68 |
|
|
|
|
|
|
18,838 |
輸入功率(W) |
16 |
2,688 |
2661 |
2,705 |
2,793 |
|
|
|
20 |
3,009 |
2959 |
2,987 |
3,067 |
3,175 |
|
|
30 |
3,905 |
3782 |
3,754 |
3,798 |
3,888 |
4,000 |
4,109 |
40 |
|
|
4,717 |
4,702 |
4,752 |
4,842 |
4,947 |
50 |
|
|
|
5,911 |
5,898 |
5,943 |
6,023 |
60 |
|
|
|
|
|
7,437 |
7,468 |
68 |
|
|
|
|
|
|
8,980 |
MLM066T4 |
制冷量(W) |
16 |
10385 |
14117 |
18110 |
22440 |
|
|
|
20 |
10143 |
13735 |
17586 |
21773 |
26371 |
|
|
30 |
9614 |
12851 |
16343 |
20167 |
24399 |
29115 |
34390 |
40 |
|
|
15063 |
18518 |
22376 |
26716 |
31612 |
50 |
|
|
|
16664 |
20143 |
24099 |
28609 |
60 |
|
|
|
|
|
21101 |
25219 |
68 |
|
|
|
|
|
|
22118 |
輸入功率(W) |
16 |
3585 |
3249 |
3065 |
3006 |
|
|
|
20 |
3895 |
3593 |
3437 |
3400 |
3457 |
|
|
30 |
4658 |
4429 |
4329 |
4334 |
4416 |
4550 |
4710 |
40 |
|
|
5314 |
5340 |
5427 |
5551 |
5686 |
50 |
|
|
|
6601 |
6674 |
6768 |
6856 |
60 |
|
|
|
|
|
8382 |
8405 |
68 |
|
|
|
|
|
|
10039 |
MLM076T4 |
制冷量(W) |
16 |
15522 |
18166 |
21614 |
25888 |
|
|
|
20 |
14984 |
17615 |
21003 |
25173 |
30146 |
|
|
30 |
13520 |
16138 |
19400 |
23330 |
27951 |
33286 |
39356 |
40 |
|
|
17610 |
21332 |
25631 |
30532 |
36055 |
50 |
|
|
|
19083 |
23093 |
, , ,
27590 |
32597 |
60 |
|
|
|
|
|
24364 |
28887 |
68 |
|
|
|
|
|
|
25674 |
輸入功率(W) |
16 |
1914 |
2426 |
2761 |
2973 |
|
|
|
20 |
2556 |
3053 |
3379 |
3587 |
3733 |
|
|
30 |
3959 |
4399 |
4681 |
4862 |
4993 |
5129 |
5325 |
40 |
|
|
5958 |
6081 |
6169 |
6278 |
6460 |
50 |
|
|
|
7643 |
7660 |
7712 |
7851 |
60 |
|
|
|
|
|
9830 |
9898 |
68 |
|
|
|
|
|
|
12275 |
以上數據為電機電壓代碼4,即380-400/3~/50HZ 額定工況:吸氣溫度20℃,無過冷度。 冷量及輸入功率數據+-5%;本表內數據若有變化,恕不另行通知。 其他工況下的冷量可從丹佛斯網址獲得:www.Danfoss.com/odsg |

MLM冷凍渦旋壓縮機
型號 |
HP |
名義冷量 |
輸入 |
能效比 * |
排量 |
排量 |
潤滑油 |
凈重 |
功率 * |
COP |
EER |
充注量 |
(含油) |
W |
Btu/h |
kW |
W/W |
Btu/h/W |
cm3/rev |
m3/h |
Litres |
kg |
R22 |
MLZ/MLM015 |
2 |
|
|
|
|
|
|
|
|
|
MLZ/MLM019 |
2 ½ |
4200 |
14 400 |
1.88 |
2.25 |
7.68 |
43.5 |
7.6 |
1.1 |
31 |
MLZ/MLM021 |
3 |
4500 |
15 300 |
2.07 |
2.16 |
7.38 |
46.2 |
8 |
1.1 |
31 |
MLZ/MLM026 |
3 ½ |
5700 |
19 500 |
2.39 |
2.39 |
8.16 |
57.1 |
9.9 |
1.1 |
31 |
MLZ/MLM030 |
4 |
6700 |
22 800 |
3.04 |
2.19 |
7.48 |
68.8 |
12 |
1.6 |
37 |
MLZ/MLM038 |
5 |
7800 |
26 600 |
3.55 |
2.2 |
7.5 |
81 |
14.1 |
1.6 |
37 |
MLZ/MLM045 |
6 |
9900 |
33 900 |
4.03 |
2.47 |
8.42 |
98.6 |
17.2 |
1.6 |
37 |
MLZ/MLM048 |
7 |
10600 |
36 100 |
4.42 |
2.39 |
8.17 |
107.5 |
18.7 |
1.6 |
37 |
MLZ/MLM058 |
7 ½ |
12000 |
41 100 |
5.31 |
2.26 |
7.73 |
126 |
21.9 |
2.7 |
44 |
MLZ/MLM066 |
9 |
14400 |
49 000 |
5.9 |
2.43 |
8.31 |
148.8 |
25.9 |
2.7 |
45 |
MLZ/MLM076 |
10 |
16600 |
56 700 |
6.71 |
2.48 |
8.45 |
162.4 |
28.3 |
2.7 |
45 |
MLZ/MLM渦旋壓縮機的運行界限在下面的圖中表示出來了,在圖中冷凝溫度和蒸發溫度是針對穩態運行工況而言的。對于瞬態工況,如啟動和化霜工況,壓縮機也許在短時間內會運行到界限之外。 下面的圖顯示了MLZ壓縮機應用R404A/507,R134a和R22不同制冷劑的運行界限。在運行界限內運行壓縮機,是安全有保障的。 應用建議:
• 最高排氣溫度:135°C •不推薦吸氣過熱度小于5K,這樣有回液的風險 • 最低和最高冷凝蒸發溫度根據運行界限而定. 
渦旋壓縮機應用范圍受到一些參數的影響,所以需要對這些參數監控以確保安全穩定的運行。 為了有良好的操作和安全運行,在接下來的部分將對這些參數提出些推薦建議。 • 制冷劑和潤滑油 • 電機電壓 • 壓縮機環境溫度 • 運行界限(蒸發溫度,冷凝溫度,回氣溫度)
制冷劑和潤滑油 概述 在選擇制冷劑時,需要考慮不同方面: • 法規要求(現在和將來) • 安全 • 制冷劑和潤滑油 • 針對所需的運行工況考慮運行界限 • 壓縮機的制冷量和效率
其他可能會影響最終選擇的因素: • 環境因素 • 制冷劑和潤滑油的標準 • 制冷劑價格 • 制冷劑容易獲得程度
R22 R22是一種HCFC制冷劑,現在仍然被廣泛使用。它具有較低的消耗臭氧潛能值(ODP)。它在將來將停止使用。請參照當地相關法律條款。 在制冷應用中使用R22,可以得到較高的排氣溫度。請仔細查看所有會影響排氣溫度的因素。
R134a R134a是一種HFC制冷劑,R134a不破壞臭氧層(ODP=0)。而且通常被認為是R12的最佳替代品。R134a是一種單一制冷劑,所以沒有溫度滑移。 對于高蒸發溫度和高冷凝溫度的應用,R134a是理想的選擇。
R404A R404A是一種HFC制冷劑。R404A不破壞臭氧層(ODP = 0)。R404A特別適合低溫應用,它也可用到中溫應用。R404A是一種混合制冷劑,有很小的溫度滑移,因此必須在液態進行充注。 但是對于絕大多數情況,這么小的溫度滑移可以被忽略。同時因為溫度滑移很小,R404A被稱為近似共沸制冷劑。
R507 R507是一種HFC制冷劑。它的性質與R404A相似。R507不破壞臭氧層(ODP=0)。如同R404A,R507特別適合低溫應用,也可用到中溫應用。 R507是非共沸制冷劑。
PVE PVE醚類油是一種新型的針對HFC制冷系統的潤滑油。PVE醚類油是一種吸水的潤滑油,如同POE酯類油。但PVE醚類油不與水發生反應;不會產生酸性物質,所以壓縮機的抽真空就變得容易了。 MLZ壓縮機采用了先進壓縮技術與PVE醚類油相結合的技術,使得穩定性和壓縮機壽命都有很好的提高。 PVE醚類油與R22兼容,這使得MLZ壓縮機成為了一個多制冷劑通用的壓縮機。
烷基苯油 烷基苯油可應用在HCFC(R22)系統中。與礦物油相比,它在可混性上具有了明顯的優勢,優越的熱穩定性,與礦物油的兼容性和良好的穩定性。 MLM系列壓縮機采用了烷基苯油,同時具有較強的價格優勢。
壓縮機環境溫度 MLZ / MLM壓縮機可應用于環境溫度從-35°C到50°C。壓縮機是設計成100%靠回氣來冷卻的。所以不需要配備冷卻風扇。 環境溫度對于壓縮機的性能影響很小。
高環境溫度 對一些壓縮機被覆蓋或在較高的環境溫度下工作時,建議檢查電源線的溫度,并請遵循相應的絕緣規范。 為了確保壓縮機內部熱保護器安全運作,壓縮機必需被冷卻到60°C以下,以確保過載保護復位。環境溫度過高,將會導致過載保護復位的時間變長。
低環境溫度 盡管壓縮機可以承受低溫環境,對于系統而言,仍然需要采取一些特殊設計以確保運行的安全性和穩定性。請參見“特殊應用建議”章節。
最高排氣溫度 排氣溫度主要取決于蒸發溫度、冷凝溫度和吸氣過熱度。排氣溫度信號應該由熱偶或者溫度傳感器采集,它們應安裝在距離壓縮機殼體15cm(6英寸)的排氣管路上。 當壓縮機運行在允許范圍內時,最高排氣溫度一定不能超出135°C (275°F)。
排氣溫度保護(DGT) 當壓縮機運行到運行界限之外時,高低壓開關不起作用時,就需要使用排氣溫度保護(DGT)來保護壓縮機。請參考下面的示例,該示例顯示了什么情況下排氣保護啟動(1區),什么情況下排氣保護不啟動(2區)。 壓縮機決不可只憑排氣溫控開關來控制。連續長時間運行在運行界限范圍之外將對壓縮機造成嚴重損傷。 排氣溫度保護附件可以從丹佛斯公司得到
 示例 1 (R22, 過熱度 = 11 K) 低壓開關設置: LP1 = 2 bar (g) (-15°C) 高壓開關設置: HP1 = 23.8 bar (g) (61°C) 當壓縮機運行到運行界限之外時,低壓、高壓開關無法充分保護壓縮機。在陰影區域,需要安裝排氣溫度保護裝置來保護壓縮機。
示例 2 (R22, 過熱度 = 11 K) 低壓開關設置: LP2 = 2.5 bar (g) (-10°C) 高壓開關設置: HP2 = 17 bar (g) (49°C) 高低壓保護可以確保壓縮機運行在運行界限內。
 高低壓保護
|
R22 |
R404A |
R134a |
高壓側工作壓力范圍 bar (g) |
7.00 - 27.9 |
7.20 - 27.7 |
4.90 - 22.1 |
低壓側工作壓力范圍 bar (g) |
0.70 - 6.4 |
1.70 - 7.2 |
0.64 - 4.0 |
高壓開關設定最大值 bar (g) |
29.8 |
29.7 |
23.6 |
低壓開關設定最小值j bar (g) |
0.5 |
1.4 |
0.45 |
推薦抽空循環開關設定 bar (g) |
比蒸發壓力低 1.5 bar |
抽空循環低壓開關設定最小值 bar (g) |
0.95 |
2 |
0.85 | *低壓開關不能有延時
內置電機保護 MLZ/MLM渦旋壓縮機在電機繞阻上配有內置的斷路保護器。該保護器為自動復位設計,且保護器包含雙金屬片動作開關。 在單相壓縮機中,內置保護器會對過大電流和高溫做出反應,該設計可在某些非正常運行下切斷電機電流,比如:堵轉、過載和風機失效等情況下。 當內置電機保護跳開后,它必須冷卻到60°C后, 電機才能再次啟動。重新啟動的時間會隨環境溫度的不同而不同,最長可能會花幾個小時。
 壓縮機焊接 進行壓縮機管路連接時,不要過分加熱壓縮機殼體,這會嚴重損壞壓縮機內部元件。強烈推薦使用隔熱罩或吸熱混合物。在焊接吸排氣口時,推薦使用以下步驟: • 確保電氣接線沒有跟壓縮機連接。 • 保護接線盒和壓縮機噴涂表面不受火焰損傷。(見下圖) • 采用適合于制冷系統的干凈銅管,并清潔所有連接處。 • 往壓縮機內吹入氮氣或CO2以避免氧化或燃燒。確保壓縮機在空氣中暴露時間不要太長。 • 建議采用雙焊頭同時加熱以保證受熱均勻。 • 在A點均勻加熱,直到達到焊接溫度,然后將焊槍移至B處,均勻加熱,直到達到焊接溫度,然后開始使用焊料。將焊槍在連接處均勻移動,焊料無需施加太多,均勻覆蓋整個接口處圓周即可。 • 將焊槍移至C處,不要停留太長時間以免將焊料帶入壓縮機。 • 將剩余焊渣用濕布或鋼絲刷清除。殘余焊渣會引起管路腐蝕。 切記:焊料或助焊劑一旦進入管路或壓縮機,由于其酸性特性,會對系統或壓縮機內部造成嚴重損害。 壓縮機內部使用的PVE油具有高吸濕性,會快速從空氣中吸收水分。壓縮機接口處密封塞應在焊接前才拿掉。 在焊拆壓縮機或任何系統部件時,必須將系統中的制冷劑從高低壓端放掉。如果不那樣做,將會造成非常嚴重的傷害。可以用壓力表進行檢測,確保系統的壓力在大氣壓水平范圍。 關于焊接所需材料的詳細信息,請咨詢產品生產商或零售商。此處未涉及到的具體應用事項,詳情請聯系丹佛斯。

|
|